Table 1 Thermal Venting Capacity
API 2000 Std Table 1 Thermal Venting Capacity
|
For Thermal Req refer below to
Table 1 Requirements for Thermal Venting Capacity
Column 1
|
Column 2
|
Column 3
|
Column 4
|
Tank Capacity
|
Inbreathing
|
|
|
|
|
|
Flash Pt > 100F
|
Flash Pt < 100F
|
BBLS
|
Gallons
|
Vaccuum
|
BP > 300F
|
BP < 300F
|
|
|
|
|
|
60
|
2500
|
60
|
40
|
60
|
100
|
4200
|
100
|
60
|
100
|
500
|
21000
|
500
|
300
|
500
|
1000
|
42000
|
1000
|
600
|
1000
|
2000
|
84000
|
2000
|
1200
|
2000
|
|
|
|
|
|
3000
|
126000
|
3000
|
1800
|
3000
|
4000
|
168000
|
4000
|
2400
|
4000
|
5000
|
210000
|
5000
|
3000
|
5000
|
10000
|
420000
|
10000
|
6000
|
10000
|
15000
|
630000
|
15000
|
9000
|
15000
|
|
|
|
|
|
20000
|
840000
|
20000
|
12000
|
20000
|
25000
|
1050000
|
24000
|
15000
|
24000
|
30000
|
1260000
|
28000
|
17000
|
28000
|
35000
|
1470000
|
31000
|
19000
|
31000
|
40000
|
1680000
|
34000
|
21000
|
34000
|
|
|
|
|
|
45000
|
1890000
|
37000
|
23000
|
37000
|
50000
|
2100000
|
40000
|
24000
|
40000
|
60000
|
2520000
|
44000
|
27000
|
44000
|
70000
|
2940000
|
48000
|
29000
|
48000
|
80000
|
3360000
|
52000
|
31000
|
52000
|
|
|
|
|
|
|